Photograph showing corroded fusible plug (Source: MOM).

Chemical Industries (Far East) Limited was fined $200,000 for a chlorine leak from a 1-ton container at its Jalan Samulun storage facility, which occurred on 4 September 2016.

In a press release on Monday (24 September), the Ministry of Manpower (MOM) shared that two emergency responders and five members of the public outside the workplace were exposed to the escaping chlorine gas in this accident.

The authority stated that chemical Industries (Far East) Limited had pleaded guilty to a charge under section 12(2) of the Workplace Safety and Health Act for failing to take reasonably practicable measures necessary to ensure the safety and health of persons who may be affected by its undertaking.

On 4 September 2016, liquid chlorine leaked from a 1-ton cylinder (“ton container”) stored in a chlorine storage facility occupied by Chemical Industries (Far East) Limited. The leak triggered an alarm from one of the chlorine detectors installed, and a worker activated the chlorine gas emergency scrubber and exhaust system.

Two workers then donned personal protective equipment and attempted to stop the leak, but were unsuccessful. Chemical Industries (Far East) Limited then called in the SCDF, and the leak was mitigated shortly after.

Two SCDF responders and five members of the public outside the workplace were momentarily exposed to the leaked chlorine gas. They were admitted to Ng Teng Fong hospital for treatment, ranging from eye irritation to difficulties in breathing, and were discharged on the same day.

According to the ministry, investigations revealed that the company had failed to maintain the integrity of the fusible plug of the chlorine ton container, which was found to be severely corroded and resulted in the leak.

A fusible plug is a fitting fastened onto the ton container to relieve the internal pressure inside the container in the event of an external fire. The company did not conduct any inspection of the fusible plugs during the external inspection of the ton containers prior to each filling, which would have revealed pre-existing corrosion damage of the fusible plug.

It then said that the company also failed to establish and implement a detailed and effective emergency response plan (“ERP”). The company’s ERP covered the scenario of a chlorine leak and assumed that the chlorine would leak slowly as a gas instead of liquid under pressure. The emergency response for liquid chlorine leak scenario was not documented under the ERP.

The ministry stated that on the day of the leak, the ton container had to be rolled over to position the leaking fusible plug to its topmost position which would convert the liquid leak to a gas leak. Converting to a gas leak would reduce the rate of chlorine mass leaking out of the corroded connection significantly, allowing emergency responders to approach the ton container and seal the corroded connection preventing further leaks.

However, when the incident occurred, the worker was unable to do so as the leaking container was stored between many other ton containers with no gaps. The company’s ERP for a liquid chlorine leak was thus ineffective.

Photograph showing the original location of the leaking ton container (container has
been removed in the above photo) (Source: MOM).

Investigations by MOM also revealed that the company failed to install its emergency scrubber and exhaust system according to design and maintain a safe air change rate in the workplace. There were 12 suction pipes located inside the perimeter of the building to extract air from the warehouse.

Some of the suction pipes within the warehouse were found to be covered with mesh filters, and no calculations were conducted to verify that these filters would not reduce the flowrate of air into the emergency scrubber and exhaust system.

Photograph showing the mesh filter screens used on suction pipe intakes (Source: MOM).

Air flowrate measurements from the suction was not conducted to verify the efficiency of the exhaust system, and investigations revealed that the rate at which the contaminated air was extracted did not meet general ventilation standards.

Er. Go Heng Huat, MOM’s Director of the Major Hazards Department, said, “The company had failed to properly maintain and store the ton containers, establish a proper emergency response plan to address chlorine leaks and implement an effective exhaust system for extracting and channelling contaminated air to the scrubber.”

“The multiple safety breaches showed a clear disregard of the hazards at the workplace and had posed a safety risk to the public. The MOM will not hesitate to prosecute companies that flout safety regulations,” he added.

Subscribe
Notify of
0 Comments
Inline Feedbacks
View all comments
You May Also Like

The more loving One

~by: Muhammad Fadli~ Recently, a Saudi blogger, Hamza Kashgari, has been deported from…

The “YouTube style of politics” in S’pore?

Is S’pore ready for the “Youtube style of politics”, as mentioned by MCYS minister Vivian Balakrishnan? Is the government ready to allow multimedia to be used for political or election campaigning?

MDA asks new website The Middle Ground to register

New social political website, The Middle Ground has been asked to register…

新马联合成立工作委会 加强两国协作抗疫

近期由于疫情肆虐,新加坡和马来西亚将联合成立一个以两国卫生部副部长为首的联合工作委员会,以强化两国应对新型冠状病毒疫情的现有合作。 卫生部昨日(11日)发布文告,宣布成立工作委员会旨在加强两国的协作与沟通,以便更好地了解2019新冠病毒的最新情况,而两国之间的高级卫生官员也会在接下来数日紧密合作,确定工作委员会的职权范围。 而我国将提名卫生部兼交通部高级政务部长蓝彬明医生担任联合主席。 文告指出,我国卫生部长颜金勇与马来西亚卫生部长祖基菲利昨日透过视讯会议,更新了各自国家的情况,并讨论其公共卫生措施、流行病学调查结果以及临床管理等课题。 两国部长一致认为,两国的卫生官员必须持续密切合作对抗疫情,尤其是两国之间拥有高流量的人流,因此双方的合作与信息共享在对抗2019新冠病毒会发挥关键作用。自疫情爆发以来,两国之间持续保持密切联系,即时共享相关跨境病例的信息。 据马国媒体《东方日报》报道,询及我国将疾病爆发应对系统升级橙色,是否会更改马来西亚前往新加坡的旅游警告,祖基菲里则表示,这都是共同工作委员会将来继续探讨的职权范围。 他指出,新马有成千上万的人因工作、家庭与旅游,需要在两国间穿梭,因此这需胥视委员会讨论后的结果,再决定是否发出旅游警告;目前仍然维持一贯的出入境标准。 截至目前,我国已累计确诊病例共47起,其中也包括跨境病例。据日前报道,一名马国人上月出席君悦酒店的国际会议,回国后被确诊,随之妹妹与岳母也证实感染。 而卫生部昨晚也证实本地再新增两起确诊病例,是一名居住在柔佛新山的35岁男子,入院前曾到圣淘沙名胜世界赌场工作,但近期内并未前往中国,于5日出现症状,9日送入陈笃生医院。 而另名确诊患者为39岁孟加拉籍客工,于6日出现症状,10日确诊,入院前曾于实里达航空园区工作,即第42起确诊病患曾工作的地方。